Zone Doubling can only be used with Normally Closed devices.
End Of Line Resistors for Non-Zone Double (2 inputs):
3.3K
E.O.L.
ANY INPUT
TERMINAL
GROUND
TERMINAL
N.C. CONTACT
WITH EOL RESISTOR
ANY INPUT
TERMINAL
3.3K
E.O.L.
GROUND
TERMINAL
N.O. CON
T
ACT
WITH EOL RESISTOR
3.3K
E.O.L.
AN
Y
INPUT
TERMINAL
GROUND
TERMINAL
ONE N.O. CON
T
ACT &
ONE N.C. CON
T
ACT
WITH EOL RESISTOR
3.3K
E.O.L.
ANY ZONE
TERMINAL
ANY COM
TERMINAL
ZONE TAMPER
EOL RESISTOR
TAMPER
CONTACT
End Of Line Resistors for Zone Double (4 inputs):
3.74K RESISTOR FOR
ZONES 1 - 2
6.98K RESISTOR FOR
ZONES 3 - 4
GROUND
TERMINAL
6.98K
E.O.L. (3 - 4)
ANY INPUT
TERMINAL
3.74K
E.O.L. (1 - 2)
3.74K
E.O.L.
AN
Y
INPU
T
TERMINA
L
AN
Y
GROUND
TERMINA
L
ZONE DOUBLED
CONFIGUR
ATION USED
AS A FIRE ZONE,
UPPER ZONE (3 - 4)
IS NOT USEABLE
Resistor Diagram:
SINGLE ZONE E.O.L.
GOLD
RED
ORANGE
ORANGE
3.3K
Ohm
ZONE DOUBLE E.O.L.
ZONES 1 - 2
ORANGE
VIOLET
YELLOW
BROWN
3.74K
Ohm
BROWN
ZONE DOUBLE E.O.L.
ZONES 3 - 4
BLUE
WHITE
GRAY
BROWN
6.98K
Ohm
BROWN