BPD series PV pumping inverter Fault diagnosis and solution
49
3. The communication
address is wrong.
4. There is strong interference
to the communication.
address.
4. Change or replace the
connection distribution or
improve the anti-interference
capability.
1. The control panel
connector is in poor contact.
2. The Hall component is
damaged.
3. The magnifying circuit is
abnormal.
1. Check the connector and
rewire.
2. Replace the Hall component.
3. Replace the main control
panel.
1. Error occurs in writing or
reading control parameters.
2. EEPROM is damaged.
1. Press STOP/RST to reset.
2. Replace the main control
panel.
1. PID feedback is offline.
2. The PID feedback source
disappears.
1. Check the PID feedback
signal line.
2. Check the PID feedback
source.
The actual running time of the
inverter is longer than the
preset running time.
Ask the supplier to adjust the
preset running time.
The inverter will report
overload pre-alarm according
to the set value.
Check the load and the overload
pre-alarm points.
The load is too heavy or
stalled.
1. Check the load and ensure it
is normal. Increase the detection
time.
2. Check whether the control
parameters are normal.
1. The control parameters of
the synchronous motors not
set properly.
2. The autotuning parameter
is not correct.
3. The inverter is not
1. Check the load and ensure it
is normal.
2. Check whether the control
parameter is set properly or not.
3. Increase the maladjustment