BPD series PV pumping inverter Commissioning guide
63
motor is drived in the 2PH control mode. For models of 380V, only 3PH motors
are applicable, that is, P02.00 can be set only to 0.
(3) Set the name plate of the motor, including P02.01, P02.02, P02.03, P02.04
and P02.05 (the maximum setting of P02.04 is 200V for the 1PH motor whose
capacitor is removed).
3. Detect water yield for water pumps
Click "Run" key, observe the running frequency and water yield. If the running
frequency or water yield is low at normal light, the motor wires may be reversed, it
is necessary to set P00.13=1 or exchange the wiring of the motor. The operation
direction of 1PH motor whose capacitor is removed can only be changed by
function code.
4. Set the operation mode
After the water yield is normal and the system runs stably, set the operation mode.
(1) Automatic operation: set P00.01=1, P05.01=1;
(2) Manual operation: set P00.01=1, P05.01=0 and P05.04=1, select S4 as the
start and stop control terminal, as shown in the preceding wiring diagram. The
system can run only after S4 is switched on. For models of 380V, you can
press the "RUN/STOP" button on the enclosure to run the inverter.