Goodrive270 series VFD for fan and pump Function parameter list
-132-
Function
code
Name Description Default
Modify
P01.04
Acceleration
P13.14
P01.23
Constant speed
In running
Deceleration
P01.10
P13.15
P01.12
P01.09
Time t
P01
.09 setting range: 0.00Hz±P00.03 (Max.
output frequency)
P01.10
setting range: 0.00±30.00s
P01.11
setting range: 0.0±100.0%
P01.12 setting range: 0.0±50.00s
P01.13
FWD/REV running
deadzone time
This function code indicates the transition time
specified in
P01.14 during FWD/REV rotation
switching. See the following figure:
Output frequency f
Forward
Reverse
Deadzone
time
Time t
Starting
frequency
Switch over after
zero frequency
Switch over after
starting frequency
Setting range: 0.0±3600.0s
0.0s ƻ
P01.14
FWD/REV running
switching mode
0: Switch at zero frequency
1: Switch at the starting frequency
2: Switch after the speed reaches the stop speed
with a delay
1 Ƽ
P01.15
Stop speed
0.00±100.00Hz
0.50Hz
Ƽ
P01.16
Stop speed
detection mode
0: Detect by the set speed (unique in space
voltage vector control mode)
1: Detect by the feedback speed
0 Ƽ
P01.17
Stop speed
detection time
0.00
±100.00s 0.50s Ƽ
P01.18
Terminal-based
running command
protection at
power-on
When the channel of running commands is
terminal control, the system detects the state of
the running terminal during power
-on.
0: The terminal running comma
nd is invalid at
power
-on. Even the running command is
considered as valid during power-on, the VFD
0 ƻ