Goodrive270 series VFD for fan and pump Function parameter list
-230-
Function
code
Name Description Default
Modify
P91.33
Integral separation
threshold
0.0
±200.0% 200.0% ƻ
P91.34
Differential filter
times
0
±40 10 ƻ
P91.35
Prior differential
processing
0:
Differential processing on feedback with priority
1: Differential processing on deviation with priority
0 ƻ
P91.36±
P91.39
Reserved
P92 group²Real-time clock and timer (available at use of LCD keypad)
Function
code
Name Description Default
Modify
P92.00
Displaying year
2020±2099YY
2020YY
ƽ
P92.01
Displaying month
and date
01.0
1±12.31MMDD
01.01MM
DD
ƽ
P92.02
Displaying day of a
week
1
±7
1±7 correspond to Monday±Sunday.
1 ƽ
P92.03
Displaying hour and
minute
00.00
±23.59HHMM
00.00 is the earliest hour and time of a day, while
23.59 is the latest hour and time of a day.
00.00HH
MM
ƽ
P92.04
Setting working days
Bit 0
±Bit 6 correspond to Monday±Sunday.
Setting instances:
Monday: 0x01
Wednesday: 0x04
From Monday to Friday: 0x1F
From Saturday to Sunday: 0x60
0 ƻ
P92.05
VFD startup hour
and minute
00.00
±23.59 HH.MM
00.00
HH.MM
ƻ
P92.06
VFD startup second
00±59S
00S
ƻ
P92.07
VFD stop hour and
minute
00.00
±23.59 HH.MM
00.00
HH.MM
ƻ
P92.08
VFD stop second
00±59S
00S
ƻ
P92.09 Clock fault
0: Disable
1: Enable
0 ƻ
P92.10
Actual second
00±59S
00S
ƽ
P92.11±
P92.19
Reserved

Table of Contents