Goodrive270 series VFD for fan and pump Basic operation guidelines
-99-
Function
code
Name Description Default
44: C_RO1 from PLC (Set P27.00 to 1.)
45: C_RO2 from PLC (Set P27.00 to 1.)
46: C_RO3 from PLC (Set P27.00 to 1.)
47: C_RO4 from PLC (Set P27.00 to 1.)
48: Fire mode activated
49: Pre-alarm of PID1 feedback too low
50: Pre-alarm of PID1 feedback too high
51: PID1 in sleep
52: PID2 in startup
53: PID2 stopped
54: Indication of run with backup pressure
55: Water shortage indication of inlet pool
56: Pre-alarm output
57: Control variable-frequency circulation motor A
58: Control variable-frequency circulation motor B
59: Control variable-frequency circulation motor C
60: Control variable-frequency circulation motor D
61±63: Reserved
P06.05
Out
put terminal polarity
selection
0x00±0x0F 0x00
P06.06
Y switch-on delay
0.000±50.000s
0.000s
P06.07
Y switch-off delay
0.000±50.000s
0.000s
P06.08
Reserved
Reserved
P06.09
Reserved
Reserved
P06.10
RO1 switch-on delay
0.000±50.000s
0.000s
P06.11
RO1 switch-off delay
0.000±50.000s
0.000s
P06.12
Reserved
Reserved
P06.13
Reserved
Reserved
P07.40
Output current status at
present fault
0x0000±0xFFFF 0
P17.13
Digital output terminal
status
0000±000F 0
5.5.13 Simple PLC
Simple PLC is a multi-step speed generator, and the VFD can change the running frequency and
direction automatically based on the running time to fulfill process requirements. Previously, such
function was realized with external PLC, while now, the VFD itself can achieve this function.
The VFD can realize 16-step speeds control, and provide four groups of acceleration/deceleration