Goodrive270 series VFD for fan and pump Function parameter list
-202-
Function
code
Name Description Default
Modify
When M=116%, protection is performed after
motor overload lasts for 1 hour; when M=200%,
protection is performed after motor overload lasts
IRUVHFRQGVDQGZKHQ0SURWHFWLRQLV
performed immediately.
1min
1h
116 % 200 %
Time t
Motor overload multiples
Setting range: 20.0%±120.0%
P12.28
Power display
calibration
coefficient of motor 2
0.00
±3.00 1.00 ƻ
P12.29
Parameter display of
motor 2
0: Display by motor type. In this mode, only
parameters related to the present motor type are
displayed.
1: Display all. In this mode, all the motor
parameters are displayed.
0 ƻ
P12.30
System inertia of
motor 2
0
±30.000kgm
2
0.000 ƻ
P12.31±
P12.32
Reserved
0
±65535 0 ƻ
P13 group²SM control
Function
code
Name Description Default
Modify
P13.00
SM injected-
current
decrease ratio
Used to set the reduction rate of the input
reactive current. When the active current of the
synchronous motor increases to some extent, the
input reactive current can be reduced to improve
the power factor of the motor.
Setting range: 0.0%
±100.0% (of the motor rated
current)
80.0% ƻ
P13.01
Detection mode of
initial pole
0: No detection
1: High
-frequency superposition
2: Pulse superposition
0 Ƽ