Goodrive270 series VFD for fan and pump Function parameter list
-203-
Function
code
Name Description Default
Modify
P13.02 Pull-in current 1
Pull
-in current is the pole position orientation
current; pull
-in current 1 is valid within the lower
limit of pull
-in current switch-over frequency
threshold. If you need to increase the start
torque, increase t
he value of this parameter
properly.
Setting range: 0.0%
±100.0% (of the motor rated
current)
20.0% ƻ
P13.03 Pull-in current 2
Pull
-in current is the pole position orientation
current; pull
-in current 2 is valid within the lower
limit of pull
-in current switch-over frequency
threshold. You do not need to change the value
in most cases.
Setting range: 0.0%
±100.0% (of the motor rated
current)
10.0% ƻ
P13.04
Source-current
switchover
frequency
0.00Hz
±P00.03(Max. output frequency) 10.00Hz ƻ
P13.05
Reserved
P13.06
High-frequency
superposition
voltage
Used to set the pulse current threshold when the
initial magnetic pole position is detected in the
pulse mode, The value is a percentage in relative
to the rated current of the motor.
Setting range: 0.0
±300.0% (of the motor rated
voltage)
100.0% Ƽ
P13.07
Reserved
P13.08
Control parameter 1
0±0xFFFF
0
ƻ
P13.09 Control parameter 2
Used to set the frequency threshold for enabling
the counter
-electromotive force phase-locked
loop in S
VC 0. When the running frequency is
lower than the value of the function code, the
phase
-locked loop is disabled; and when the
running frequency is higher than that, the
phase
-locked loop is enabled.
Setting range: 0±655.35
50.00 ƻ
P13.10
Reserved
0.0±359.9
0.0
ƻ
P13.11
Maladjustment
Used to adjust the responsiveness of
0.5s
ƻ