Goodrive270 series VFD for fan and pump    Function parameter list 
-148- 
Name  Description  Default 
P04.05±P02.16 (Rated 
 
 setting range: 0.0%±
110.0% (of the rated 
voltage of motor 1) 
P04.09 
V/F slip 
compensation gain 
of motor 1 
Used to compensate for the motor rotating speed 
change caused by load change in the space 
voltage vector mode, and thus improve the 
rigidity of the mechanical characteristics of the 
motor. You need to calculate the rate
d slip 
frequency of the motor as follows: 
 
f=f
b
-n*p/60 
b
 is the rated frequency of the motor, 
corresponding to function code 
P02.02. n is the 
rated rotating speed of the motor, corresponding 
to function code 
P02.03. p is the number of pole 
pairs of the motor. 100.0% corresponds to the 
rated slip frequency ᶭ
f of motor 1. 
Setting range: 0.0±200.0% 
0.0%  ƻ 
P04.10 
Low-frequency 
oscillation control 
In space voltage vector control mode, the motor, 
especially the large
-power motor, may 
experience current oscillation at certain 
frequencies, which may cause unstable motor 
running, or even VFD overcurrent. You can 
adjust the two function codes properly to 
eliminate such phenomenon.
 
 setting range: 0±100 
 setting range: 0±100 
 setting range: 0.00Hz±P00.03 (Max. 
10  ƻ 
P04.11 
High-frequency 
oscillation control 
factor of motor 1 
10  ƻ 
P04.12 
Oscillation control 
threshold of motor 1
30.00Hz  ƻ 
P04.13 
motor 2 
This group of function code defines the V/F curve 
of motor 2 to meet the needs of differe
nt loads. 
-line V/F curve 
-point V/F curve 
-down V/F curve (power of 1.3) 
-down V/F curve (power of 1.7) 
-down V/F curve (power of 2.0) 
5: Customized V/F curve (V/F separation)
 
Note: Refer to the description for P04.00. 
0  Ƽ