Goodrive270 series VFD for fan and pump Function parameter list
-167-
Function
code
Name Description Default
Modify
Note: Restoring the default values may delete
the user password. Exercise caution when
using this function.
P07.01 Parameter copy
Used to set the parameter copy mode.
0:
No operation
1: Upload parameters from the local address to
the keypad
2: Download parameters (including motor
parameters) from the keypad to the local address
3: Download parameters (excluding group
P02.00) from the keypad to the local address
4: Download
parameters (only including group
P02) from the keypad to the local address
Note: After any operation among 1
±4 is
completed, the parameter restores to 0. The
upload and download functions are not
applicable to group P29.
0 Ƽ
P07.02
Key function
selection
Range: 0x00
±0x27
Ones place: Function of
QUICK/JOG
0: No function
1: Jog
2: Reserved
3: Switch between forward and reverse rotating
4: Clear the
UP/DOWN setting
5: Coast to stop
6: Switch command channels in sequence
7: Res
erved
Tens place: Reserved
0x01 Ƽ
P07.03
Sequence of
switching
running-command
channels by
pressing QUICK
When
P07.02=6, set the sequence of switching
running
-
command channels by pressing this key.
.H\SDGĺ7HUPLQDOĺ&RPPXQLFDWLR
n
.H\SDGĸĺ7HUPLQDO
.H\SDGĸĺ&RPPXQLFDWLRQ
7HUPLQDOĸĺ&RPPXQLFDWLRQ
0 ƻ
P07.04
Stop function validity
of STOP/RST
Used to specify the stop function validity of
STOP/RST
. For fault reset, STOP/RST is valid
in any conditions.
0: Valid only for keypad control
0 ƻ