Goodrive270 series VFD for fan and pump Function parameter list
-176-
Function
code
Name Description Default
Modify
1: Modbus communication
2:
PROFIBUS/CANopen/DeviceNet
communication
3: Ethernet communication
4: EtherCAT/PROFINET co
mmunication
Tens place: indicates whether to enable
switchover during running
0: Disable
1: Enable
P08.32
FDT1 electrical level
detection value
When the output frequency exceeds the
corresponding frequency of FDT electrical level,
the multifunction
digital output terminal
continuously outputs the signal of
"Frequency
level detection FDT
". The signal is invalid only
when the output frequency decreases to a value
lower than the frequency corresponding to (FDT
electrical level
²FDT lagging detection value).
Time t
Output frequency f
FDT level
FDT lag
Y1,
RO1, RO2
Time t
P08.32
setting range: 0.00Hz±P00.03 (Max.
output frequency)
P08.33
setting range: 0.0±100.0% (FDT1
electrical level)
P0
8.34 setting range: 0.00Hz±P00.03 (Max.
output frequency)
P08.35
setting range: 0.0±100.0% (FDT2
electrical level)
50.00Hz ƻ
P08.33
FDT1 lagging
detection value
5.0% ƻ
P08.34
FDT2 electrical level
detection value
50.00Hz ƻ
P08.35
FDT2 lagging
detection value
5.0% ƻ
P08.36
Detection value for
frequency being
reached
When the output frequency is within the detection
range, the multifunction digital output terminal
outputs the signal of "Frequency reached".
0.00Hz ƻ

Table of Contents