Goodrive270 series VFD for fan and pump Function parameter list
-179-
Function
code
Name Description Default
Modify
2: Valid during running, cleared after a stop
command is received
LED thousands place: Indicates whether to
enable the i
ntegral function through the ġ/Ģ
key and digital potentiometer.
0: Disable the integral function
1: Enable the integral function
P08.43
Keypad digital
potentiometer
integral rate
0.01
±10.00s 0.10s ƻ
P08.44
UP/DOWN terminal
control setting
0x000
±0x221
Ones place: Frequency s
etting selection
0: The setting made through
UP/DOWN is valid.
1: The setting made through
UP/DOWN is
invalid.
Tens place: Frequency control selection
0: Valid only when
P00.06=0 or P00.07=0
1: Valid for
all frequency setting methods
2: Invalid for multi
-step speed running when
multi
-step speed running has the priority
Hundreds place: Action selection for stop
0: Setting is valid.
1: Valid during running, cleared after stop
2: Valid during running, cleared
after a stop
command is received
0x000 ƻ
P08.45
Frequency
increment integral
rate of the UP
terminal
0.01
±50.00Hz/s 0.50Hz/s
ƻ
P08.46
Frequency integral
rate of the DOWN
terminal
0.01
±50.00Hz/s 0.50Hz/s
ƻ
P08.47
Action selection at
power-off during
frequency setting
0x000
±0x111
Ones place: Action selection at power
-off during
frequency adjusting through digitals.
0: Save the setting at power
-off.
1: Clear the setting at power
-off.
Action selection at power-off during frequency
0x000 ƻ

Table of Contents