Goodrive270 series VFD for fan and pump Function parameter list
-190-
Function
code
Name Description Default
Modify
constant bus voltage control method, which
makes the motor
in power generation state. The
regenerative power can maintain the bus voltage
to ensure normal running of the VFD until the
recovery of power.
Voltage class
220V
380V
660V
Frequency
decrease at
sudden power
failure
260V 460V 800V
Note:
This function can avoid VFD stop that is made
for the purpose of protection in grid switchover.
This function can be enabled only when the
input phase loss protection function is disabled.
P11.02
Enabling
energy-
consumption
braking for stop
Indicates whether to enabl
e energy-
consumption
braking when the VFD is in stopped state.
0: Enable
1: Disable
1 Ƽ
P11.03
Overvoltage stalling
protection
0: Disable
1: Enable
Overvoltage
stalling protection
point
Output
frequency
Time t
Time t
DC bus voltage V
If the bus voltage exceeds the overvoltage
stalling
protection point, the motor is in power
generation state, and the overvoltage stalling
protection function takes effect to regulate output
frequency (that is, consume unnecessary
regenerative electricity).
1 ƻ
P11.04
Overvoltage stalling
protection voltage
120±150% (standard bus voltage) (380V)
136%
ƻ
120±150% (standard bus voltage) (220V)
120%