Goodrive270 series VFD for fan and pump    Function parameter list 
-193- 
Name  Description  Default 
P11.11 
-
alarm 
detection threshold 
-alarm signal will be outputted if 
the output current of the VFD or motor is lower 
than underload pre
-alarm detection level 
P11.11), and the duration exceeds underload 
-alarm detection time (P11.12). 
 setting range: 0±P11.09 
P11.12 setting range: 0.1±3600.0s 
50%  ƻ 
P11.12 
-
detection time 
1.0s  ƻ 
P11.13 
action upon fault 
occurring 
Used to set the action of fault output terminals at 
undervoltage and fault reset.
 
±0x11 
 
0: Act upon an undervoltage fault
 
ot act upon an undervoltage fault 
 
0: Act during automatic reset
 
1: Do not act during the automatic reset period 
0x00  ƻ 
P11.14 
Speed deviation 
±50.0% 
Used to set the speed deviation detection value. 
10.0%  ƻ 
P11.15 
Speed deviation 
detection time 
±10.0s (0.0 indicates no speed deviation 
 
Used to set the speed deviation detection time.
 
Note: Speed deviation protection is invalid 
when 
P11.15=0.0. 
Speed
Actual detection
value
Set detection
value
Time t
t1
t2
t2=P11.15
t1<t2, so the VFD continues running
dEu
Running Fault output
 
2.0s  ƻ 