Goodrive270 series VFD for fan and pump Function parameter list
-235-
Name Description Default
P94.39
Water level signal
input selection of
inlet pool
0 ƻ
P94.40
Water level upper
±100.0% 60.0% ƻ
P94.41
Water level lower
0±100.0% 40.0% ƻ
P94.42
Water shortage level
of inlet pool
±100.0% 20.0% ƻ
P94.43
Backup pressure
±100.0% (relative to PID1 max. value) 0.0% ƻ
P94.44
PID1 feedback too
±100.0% (relative to PID1 max. value) 10.0% ƻ
P94.45
Delay of PID1
feedback too low
±3600.0s
Corresponding terminal output that is set when
PID1 feedback value is less than P94.44 and this
situation lasts the time longer than P94.45.
500.0s ƻ
P94.46
PID1 feedback too
±100.0% (relative to PID1 max. value) 80.0% ƻ
P94.47
Delay of PID1
feedback too high
±3600.0s
Corresponding terminal output that is set when
PID1 feedback value is greater than P94.46 and
this situation lasts the time longer than P94.47.
500.0s ƻ
P94.48
DEC time of
±600.0s 2.0s ƻ
P94.49
ACC time with water
pump frequency
±3600.0s
Model
ƻ
P94.50
DEC time with water
pump frequency
±3600.0s
Model
ƻ
P94.51±
Reserved