EasyManuals Logo

INVT GD270-090-4 User Manual

INVT GD270-090-4
336 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #247 background imageLoading...
Page #247 background image
Goodrive270 series VFD for fan and pump Function parameter list
-237-
Function
code
Name Description Default
Modify
P96.03
Water pipe soft
padding function
0: Disable
1: Enable
0 ƻ
P96.04
Reference frequency
for soft padding
0.00
±P00.03 30.00Hz ƻ
P96.05
Duration of
reference frequency
for soft padding
0.0
±6000.0s 10.0s ƻ
P96.06
Soft padding cutoff
detection level
The PID function is valid when the feedback
value is greater than the value of this function
code.
Range: 0.0±100.0%
30.0% ƻ
P96.07±
P96.09
Reserved
P96.10
Enabling freezing
protection
Freezing protection
:
The freezing protection signal is activ
ated when
the detected temperature is lower than the
protection threshold; this signal is ignored if the
VFD is running.
If the run command is received after the
protection has been activated, the protection is
terminated and the run command is executed. I
f
a stop command is received after the protection
has been activated, the motor is stopped and
automatic protection is disabled. Automatic
protection can be enabled only when the
temperature is higher than the protection
threshold.
0: Disable
1: Enable
0 ƻ
P96.11
Temperature sensor
type
Select current output for AO, connect one end of
the temperature resistor to AI1 and AO1 and the
other end to GND.
0: Disable
1: PT100
2: PT1000
3: KTY84
0 ƻ

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT GD270-090-4 and is the answer not in the manual?

INVT GD270-090-4 Specifications

General IconGeneral
BrandINVT
ModelGD270-090-4
CategoryWater Pump
LanguageEnglish

Related product manuals