Goodrive270 series VFD for fan and pump Function parameter list
-239-
Function
code
Name Description Default
Modify
P96.24
Forward run duration
for pump cleaning
0.0
±3600.0s 5.0s ƻ
P96.25
Reverse run
duration for pump
cleaning
0.0
±3600.0s 5.0s ƻ
P96.26
Forward/reverse run
interval for pump
cleaning
0.0
±3600.0s 1.0s ƻ
P96.27
Number of pump
cleaning cycles
1
±1000 1 ƻ
P96.28
Motor stalling
function selection
Prerequisite for selecting the function: The VFD
exceeds the stalling current limit, the output
frequency is lower than the stalling frequ
ency
upper limit, and the duration of this situation
exceeds the stalling time.
0: Disable
1: Alarm
2: Faulty
0 ƻ
P96.29 Stalling current limit
0.0
±1600.0%
Note: 100.0% corresponds to the motor rated
current.
200.0% ƻ
P96.30
Stalling frequency
upper limit
0.00
±P00.06
It cannot be lower than 10Hz.
15Hz ƻ
P96.31
Stalling detection time
0.0±3600.0s
2.0s
ƻ
P96.32
Motor dry pumping
function selection
0: Disable
1: Alarm
2: Faulty
0 ƻ
P96.33
Current limit for
motor dry pumping
0.0%
±100.0%
Note: 100.0% corres
ponds to the motor rated
current.
0.0% ƻ
P96.34
Detection time for
motor dry pumping
0.0
±3600.0s 2.0s ƻ
P96.35
Motor
overtemperature point
When the detected motor temperature is higher
than this value, a fault is reported.
110.
P96.36±
P96.59
Reserved