Goodrive270 series VFD for fan and pump Basic operation guidelines
-69-
autotuned for SMs. P02.23 can be obtained through calculation.
Motor autotuning can be carried out on the present motor only. If you need to perform autotuning
on the other motor, switch the motor through selecting the switch-over channel of motor 1 and
motor 2 by setting the ones place of P08.31.
Related parameter list:
Function
Name Description Default
P00.01
Channel of running
commands
0: Keypad
1: Terminal
0
P00.15
Motor parameter
autotuning
0: No operation
1: Rotary autotuning 1.
Comprehensive motor parameter autotuning. It
is recommended to use rotating autotuning
when high control accuracy is required.
2: Static autotuning 1 (comprehensive
autotuning); static autotuning 1 is used when
the motor cannot be disconnected from load.
3: Static autotuning 2 (partial autotuning); when
the present motor is motor 1, only P02.06,
P02.07, and P02.08 are autotuned; when the
present motor is motor 2, only P12.06, P12.07,
and P12.08 are autotuned.
4: Rotary autotuning 2, which is similar to rotary
autotuning 1 but only valid for AMs.
5: Sta
tic autotuning 3 (partial autotuning), which
is valid only for AMs.
0
P02.00 Type of motor 1
0: Asynchronous motor (AM)
1: Synchronous motor (SM)
0
P02.01 Rated power of AM 1 0.1±3000.0kW
Model
P02.02 Rated frequency of AM 1
0.01Hz±P00.03(Max. output frequency) 50.00Hz
P02.03 Rated speed of AM 1 1±60000rpm
Model
P02.04 Rated voltage of AM 1 0±1200V
Model
P02.05 Rated current of AM 1 0.8±6000.0A
Model