Goodrive270 series VFD for fan and pump Basic operation guidelines
-71-
Function
code
Name Description Default
3: Ethernet communication
4: EtherCAT/PROFINET communication
Tens place: indicates whether to enable
switchover during running
0: Disable
1: Enable
P12.00 Type of motor 2
0: Asynchronous motor (AM)
1: Synchronous motor (SM)
0
P12.01 Rated power of AM 2 0.1±3000.0kW
Model
depended
P12.02 Rated frequency of AM 2
0.01Hz±P00.03(Max. output frequency) 50.00Hz
P12.03 Rated speed of AM 2 1±60000rpm
Model
depended
P12.04 Rated voltage of AM 2 0±1200V
Model
depended
P12.05 Rated current of AM 2 0.8±6000.0A
Model
depended
P12.06
Stator resistance of AM
2
0.001±ȍ
Model
depended
P12.07 Rotor resistance of AM 2
0.001±ȍ
Model
depended
P12.08
Leakage inductance of
AM 2
0.1±6553.5mH
Model
depended
P12.09
Mutual inductanc
e of AM
2
0.1±6553.5mH
Model
depended
P12.10 No-load current of AM 2 0.1±6553.5A
Model
depended
P12.15 Rated power of SM 2 0.1±3000.0kW
Model
depended
P12.16 Rated frequency of SM 2
0.01Hz±P00.03(Max. output frequency) 50.00Hz
P12.17
Number of pole pairs of
SM 2
1±50 2
P12.18 Rated voltage of SM 2 0±1200V
Model
depended
P12.19 Rated current of SM 2 0.8±6000.0A
Model
depended