Goodrive270 series VFD for fan and pump Basic operation guidelines
-73-
Standby
Run status
before power failure
0
1
P01.21
(restart at power-cut)
Waiting time of restart at
power-cut>P01.22
0
1
2
Stop
Run
0
1
P01.18
(Power-on terminal running protection
selection)
Delay time of restart
>P01.23
N
Y
Y
N
Restart after
power-cut
Run
Stop
Whether FWD/REV
running terminal command
is valid
N
Run
Y
P00.01
Running command channel
Keypad
Communi
cation
Terminal
3. Logic diagram for start after automatic fault reset
VFD fault
In running
Automatic reset times
of VFD fault<P08.28
Automatic reset
interval of VFD
fault>P08.29
Restart after VFD
fault reset
Display the fault
code and stop
N
N
Y
Y
Related parameter list:
Function
Name Description Default
P00.01
Channel of running
commands
0: Keypad
1: Terminal
0
P00.11
ACC time 1 0.0±3600.0s
Model
P00.12
DEC time 1 0.0±3600.0s
Model
P01.00
Start mode
0: Direct start
1: Start after DC braking
2: Speed tracking restart 1
Note: In SVC
0, speed tracking cannot be
selected, indicating P01.00 can be 0 or 1.
0
P01.01
Starting frequency of direct
0.00±50.00Hz 0.50Hz