ACC time means the time needed if the inverter
speeds up from 0Hz to the Max. One (P00.03).
DEC time means the time needed if the inverter
speeds down from the Max. Output frequency to
0Hz (P00.03).
Goodrive200A series inverters define four
groups of ACC/DEC time which can be selected
by P05. The factory default ACC/DEC time of the
inverter is the first group.
Setting range of P00.11 and P00.12:0.0~3600.0s
0: Runs at the default direction, the inverter runs
in the forward direction. FWD/REV indicator is
off.
1: Runs at the opposite direction, the inverter
runs in the reverse direction. FWD/REV indicator
is on.
Modify the function code to shift the rotation
direction of the motor. This effect equals to the
shifting the rotation direction by adjusting either
two of the motor lines (U, V and W). In keypad
control, the motor rotation direction can be
changed by QUICK/JOG on the keypad. Refer to
parameter P07.02.
Note: When the function parameter comes back
to the default value, the motor’s running direction
will come back to the factory default state, too. In
some cases it should be used with caution after
commissioning if the change of rotation direction
is disabled.
2: Forbid to run in reverse direction: It can be
used in some special cases if the reverse running
is disabled.
0 ○
P00.14