Goodrive200A inverters Function parameters
70
Function
code
Name Detailed instruction of parameters
Default
value
Modify
Sudden jumping frequencytraverse range AW
×sudden jumping frequency range P08.16.
When run at the traverse frequency, the value
which is relative to the sudden jumping
frequency.
The raising time of the traverse frequency: The
time from the lowest point to the highest one.
The declining time of the traverse frequency: The
time from the highest point to the lowest one.
The setting range of P08.15: 0.0~100.0%
(relative to the set frequency)
The setting range of P08.16: 0.0~50.0%
(relative to the traverse range)
The setting range of P08.17: 0.1~3600.0s
The setting range of P08.18: 0.1~3600.0s
P08.19
Setting
length
The function codes of setting length, actual
length and unit pulse are mainly used to control
the fixed length.
The length is counted by the pulse signal of HDI
terminals input and the HDI terminals are needed
to set as the length counting input.
Actual lengththe length counting input pulse
/unit pulse
When the actual length P08.20 exceeds the
setting length P08.19, the multi-function digital
output terminals will output ON.
Setting range of P08.19: 0~65535m
Setting range of P08.20:0~65535m
Setting range of P08.21:1~10000
Setting range of P08.22:0.01~100.00cm
Setting range of P08.23:0.001~10.000
Setting range of P08.24:0.001~1.000
0m
P08.20
A
ctual length
0m
P08.21
Pulse per
rotation
1
P08.22
Alxe
perimeter
10.00
cm
P08.23
L
ength ratio
1.000
P08.24
Length
correcting
coefficient
1.000
P08.25
Setting
counting
value
The counter works by the input pulse signals of
the HDI terminals.
When the counter achieves a fixed number, the
multi-function output terminals will output the
signal offixed counting number arrival” and the
counter go on working; when the counter
achieves a setting number, the multi-function
output terminals will output the signal of “setting
counting number arrival”, the counter will clear all
0
P08.26
Reference
counting
value
0