7.3.2 ASCII mode
7.3.2.1 Command code 03H (0000 0011), reading N words (continuously reading a
maximum of 16 words)
For example, for the VFD whose slave address is 01H, the start address of internal storage is
0004, to read two words continuously, the structure of this frame is as follows:
ASCII master command (from the master
to the VFD)
ASCII slave response (from the VFD to the
master)
START
‘:’
START
‘:’
ADDR
‘0’
ADDR
‘0’
‘1’
‘1’
CMD
‘0’
CMD
‘0’
‘3’
‘3’
Start address MSB
‘0’
Number of bytes
‘0’
‘0’
‘4’
Start address LSB
‘0’
MSB of data in 0004H
‘1’
‘4’
‘3’
Data count MSB
‘0’
LSB of data in 0004H
‘8’
‘0’
‘8’
Data count LSB
‘0’
MSB of data in 0005H
‘0’
‘2’
‘0’
LRC CHK Hi
‘F’
LSB of data in 0005H
‘0’
LRC CHK Lo
‘6’
‘0’
END Hi
CR
LRC CHK Hi
‘5’
END Lo
LF
LRC CHK Lo
‘D’
END Hi
CR
END Lo
LF
7.3.2.2 Command word 06H (0000 0110), writing a word
For example, to write 5000 (1388H) to 0004H of the VFD whose address is 02H, the frame
structure is as follows.
ASCII master command (from the master
to the VFD)
ASCII slave response (from the VFD to the
master)
START
‘:’
START
‘:’
ADDR
‘0’
ADDR
‘0’
‘2’
‘2’
CMD
‘0’
CMD
‘0’
‘6’
‘6’

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT Goodrive18 Series and is the answer not in the manual?

INVT Goodrive18 Series Specifications

General IconGeneral
BrandINVT
ModelGoodrive18 Series
CategoryIndustrial Electrical
LanguageEnglish

Related product manuals