EasyManuals Logo

ITRON ACE6000 User Manual

ITRON ACE6000
85 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #79 background imageLoading...
Page #79 background image
Erreur ! Utilisez l'onglet Accueil pour appliquer Heading 1 au texte que vous souhaitez faire apparaître ici.
read the Total Energy Registers (TER) values
read all instantaneous values
read the meter status values and its configuration
erase any non-fatal alarms
7. Carry out the LCD test and confirm all the display segments and annunciator icons are lit.
8. Wait for approx 15 minutes while the meter operates.
9. Check the TER values have incremented from their initial values.
10. Check the maximum demand value is consistent with the applied load.
11. Re-check meter status.
If the support tool 'Toolbox' application is available:
1. Use the Toolbox functions to verify all aspects of meter operation.
2. Save and print the results as evidence of correct operation.
10.10. Sealing the meter
Before leaving the installation site, fit the terminal cover, and seal the meter against unauthorised access or
tampering by fitting wire or plastic seals in the following locations:
1
Battery holder
Underneath hinged front panel
2
Main cover
3
Hinged front panel
4
Terminal cover

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ITRON ACE6000 and is the answer not in the manual?

ITRON ACE6000 Specifications

General IconGeneral
Voltage230V AC
Frequency50/60 Hz
DisplayLCD
CommunicationRS-485
Temperature Range+55°C
Current5A
Frequency Range45Hz to 65Hz
Storage Temperature+70°C
Humidity95% RH (non-condensing)

Related product manuals