Mean value
Mean values are formed over an adjustable period
for the current, voltage and power measured values.
The mean values are identified with a bar above
the measured value.
The averaging time can be selected from a list of nine
fixed averaging times.
Current averaging time (addr. 040)
Power averaging time (addr. 041)
Voltage averaging time (addr. 042)
Setting Baud rate
0 300 Baud
1 600 Baud
2 1200 Baud
3 2400 Baud
4 4800 Baud
5 9600 Baud
6 19200 Baud
7 38400 Baud
Baud rate (addr. 001)
A common baud rate is adjustable for the M-Bus inter-
faces. The baud rate must be chosen to be a uniform
value in the network. The parameter data bits (8), parity
(even) and stop bits (1) are permanently set.
Setting Averaging time/sec.
0 5
1 10
2 15
3 30
4 60
5 300
6 480 (factory setting)
7 600
8 900
m
Note for setting the baud rate:
The baud rate is set directly on the device.
It is not possible to set the baud rate via
M-Bus !