SECTION 3 - OPTIVIEW DISPLAY MESSAGES
FORM 160.10-O1
ISSUE DATE: 4/27/2018
3
of a starter initiated shutdown with twenty (20) sec-
onds of the shutdown, the microboard assumes the
cause is not forthcoming and that message is re-
placed with this message. The chiller can be started
when the motor controller LCSSS stop contacts close.
A missing interlock jumper between starter logic/
trigger board J1-1 and J1-12 will also produce this
message.
LCSSS – POWER FAULT
The liquid cooled solid state starter logic/trigger board
has detected that the compressor motor current in one
or more phases has decreased to less than 10% of the
FLA for a minimum of one (1) line cycle. This check is
inhibited during the first four (4) seconds of chiller op-
eration and until the motor current is above 25% of the
Job FLA. The chiller will automatically restart upon
completion of SYSTEM COASTDOWN.
LCSSS – LOW PHASE (X) TEMPERATURE
SENSOR
The liquid cooled solid state starter logic/trigger board
has detected that the temperature of the starter phase
A, B or C (designated as X above) Silicon Controlled
Rectifier (SCR) Module has decreased below 37°F.
This would generally be indicative of a disconnected
or defective sensor. If all three SCR modules are indi-
cating a temperature of less than 37°F, the SCR module
cooling pump turns on. This is accomplished by dis-
connecting all three sensors. This feature allows ser-
vice technicians to run the cooling pump while filling
the cooling system by disconnecting plugs P2, P3 and
P4 in the LCSSS.
LCSSS – RUN SIGNAL
The liquid cooled solid state starter receives two start
signals from the OptiView Control Center simultane-
ously; one via the serial communications link and one
via the start relay TB6-24 in the control center. If the
signals are not received within 5 seconds of one anoth-
er, a cycling shutdown is performed and this message
is displayed. This is generally indicative of defective
wiring.
LCSSS – INVALID CURRENT SCALE
SELECTION
There is an invalid compressor motor current scale
jumper combination installed in the liquid cooled solid
starter logic/trigger board, J1. Jumper combination de-
termines allowable 100% FLA setpoint range; 7L - 35
to 260A, 14 L- 65 to 510A, 26L - 125 to 850A and
33L-215 to 1050A. The chiller will be permitted to
start when the jumpers are configured correctly. Re-
fer to the Solid State Starter MOD “B” – Operation/
Service Manual (Form 160.00-O2) for valid jumper
configurations.
LCSSS – PHASE LOCKED LOOP
The liquid cooled solid state starter logic/trigger board
phase locked loop circuit was not able to maintain lock
with phase A of the power line. This could be caused
by a power line anomaly such as sag or jitter. A power
line frequency jitter of up to 3 Hz/second can be toler-
ated. The chiller will automatically restart when lock
has resumed.
LCSSS – LOGIC BOARD PROCESSOR
Communication between the V25 Microprocessor and
Digital Signal Processor (DSP) on the liquid cooled
solid state starter logic/trigger board has been inter-
rupted. The chiller will automatically restart when
communications are restored.
LCSSS – LOGIC BOARD POWER SUPPLY
This message is displayed after a loss of power. Fol-
lowing application of power, this message is displayed
and a snapshot of the LCSSS parameters and time of
power failure are sent to the control center.
LCSSS – PHASE LOSS
The liquid cooled solid state starter logic/trigger board
has detected the line-to-line RMS voltage in any phase
has decreased to 30% or below the lowest value of the
programed voltage range. If the programmed voltage
range is DISABLED, a value of 60VAC is used as the
threshold. The chiller will automatically restart when
the line voltage is higher than the shutdown threshold.
Service technicians program the voltage range follow-
ing instructions in the Solid State Starter MOD “B” –
Operation/Service Manual (Form 160.00-O2).
LCSSS – LOW SUPPLY LINE VOLTAGE
The liquid cooled solid state starter logic/trigger board
has detected that the compressor motor AC power line
voltage, in any phase, decreased below the low line
voltage threshold continuously for twenty (20) sec-
onds. The chiller will automatically restart when the
voltage in all phases reaches the restart level. Refer to
Table 7 for Voltage Thresholds.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls YORK OPTIVIEW CONTROL CENTER and is the answer not in the manual?

Johnson Controls YORK OPTIVIEW CONTROL CENTER Specifications

General IconGeneral
BrandJohnson Controls
ModelYORK OPTIVIEW CONTROL CENTER
CategoryControl Panel
LanguageEnglish

Related product manuals