SECTION 2 - OPTIVIEW OPERATION
is increased, the shutdown threshold is 36.0°F (water)
or 6.0°F (brine) for the next ten (10) minutes. If Smart
Freeze is enabled, the threshold is 34.0°F for the next
ten minutes. After ten minutes have elapsed, the shut-
down threshold becomes the programmed setpoint
value.
Remote Analog Input Range
Access Level Required: OPERATOR
This setpoint defines the remote signal range applied
for remote reset of the leaving chilled liquid tempera-
ture setpoint and current limit setpoint in analog remote
mode. If the remote signal is 0-10VDC or 0-20mA, this
setpoint must be programmed for 0-10VDC. If the re-
mote signal is 2-10VDC or 4-20mA, this setpoint must
be programmed for 2-10VDC.
Local Motor Current Limit
Access Level Required: OPERATOR
Allows the maximum allowed motor current (as a
percentage of FLA) to be adjusted. When the motor
current reaches this value, the pre-rotation vanes will
not open further. If the motor current rises above this
value, the pre-rotation vanes will close to reduce cur-
rent to this setpoint. This value is adjustable from 30 to
100%, with 100% as the default setting.
Pulldown Demand Limit
Access Level Required: OPERATOR
This setpoint limits the motor current (programmed as
a percentage of FLA) during the specified pulldown
demand time. This value will override the motor cur-
rent limit value during this time period. This function is
used to provide energy savings following chiller start-
up and is adjustable from 30 to 100%, with 100% as
the default setting.
Pulldown Demand Time
Access Level Required: OPERATOR
This setpoint programs the period of time the pulldown
demand limit will be in effect after the chiller starts.
The pulldown demand time is adjustable from 0 to 255
minutes, with 0 minutes as the default.
Print
Access Level Required: VIEW
This function will generate a “Setpoints” print report.
Change Setpoint
Access Level Required: VIEW
Allows user to enter login password to change motor
settings. This button is only present at the “View” ac-
cess level.
NAVIGATION
Home
Access Level Required: VIEW
Returns the display to the Home screen.
Setup
Access Level Required: VIEW
Advances to the Setup sub-screen, allowing setup of
general system parameters.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls YORK OPTIVIEW CONTROL CENTER and is the answer not in the manual?

Johnson Controls YORK OPTIVIEW CONTROL CENTER Specifications

General IconGeneral
BrandJohnson Controls
ModelYORK OPTIVIEW CONTROL CENTER
CategoryControl Panel
LanguageEnglish

Related product manuals