Technical Specification
1 --- 2
1.5 SetPointoftheSafetyReliefValve
80---125 psig Compressor Unit --- Activating pressure 155 psig....
1.6 Installation Requirements
Max. height above sea level of the place of installation 3000 ft...
(for all heights above please contact authorized KAESER distributor)
Min. ambient temperature 40 EF.............................
Max. ambient temperature 115 EF............................
Min. cooling air/inlet air temperature 40 EF....................
Max. cooling air/inlet air temperature 115 EF...................
Air inlet opening 14 sq.ft.......................................
Exhaust air for solution A (see chapter 6.1):
Forced ventilation with exhaust ventilator 11770 cfm at static pressure of.............
0.4 inches water column
Exhaust air for solution B (see chapter 6.1):
Exhaust air used for space heating:
Heating duct w x h 27 1/2 x 27 1/2.........................
1.7 Oil Capacities
Total oil capacities 7 3/8 gal..................................
After oil change or after long period of storage
Quantity required for prelubrication of the airend 1 quart...........
(Refer to chapter 7.8.1)
Difference in oil volume between minimum and maximum levels
Top off volume 4.25 quart......................................

Table of Contents