EasyManuals Logo

Kamstrup flowIQ 3100 User Manual

Kamstrup flowIQ 3100
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #28 background imageLoading...
Page #28 background image
TECHNICAL DESCRIPTION flowIQ® 3100
28 Kastup A/S • Tehial Desiptio • 5512-1242_D_GB • 09.2016
9.7.4 Info codes
The info codes consist of 7 separate text signs (framed in the above sketch), which indicate a special condition
in the meter. The signs flash when active. If not, they are OFF.
The individual info codes are described below:
Info code - ERROR
This info code is not used.
Info code - LEAK
This info code activates if the water in the water meter is never stagnant. Possible un-tight connections,
running cisterns, un-tight safety valves in hot water tanks, or other untightnesses will have the result that
the meter registers water flow 24 hours a day.
If the water meter has not registered minimium one continuous hour without water flow within the latest
24 hours, this is a sign of a leakage in the water installation. The alarm automatically disappears after an hour
without flow in the meter.
The sensivity of the leak surveillance can be selected by the customer when submitting the order, and later
by Metertool. The following options are available:
Leak surveillance
N=
Constant minimum flow alarm is activated at:
0
OFF
1
Continuous flow > 0.5 % of Q
3
2
Continuous flow > 1.0 % of Q
3
3
Continuous flow > 2.0 % of Q
3
4
Continuous flow > 0.25 % of Q
3
5
Continuous flow > 0.1 % of Q
3
The utility must be aware that there can be water consumption all the 24 hours in households with many
residents. This means that there will not be any hours without flow, and flowIQ® 3100 will set an alarm for
this 24-hour period. Users and water utilities must, therefore, be critical of the leakage alarm.
The leakage alarm is saved with a date stamp in both daily register for 460 days and in monthly register for
36 months. Furthermore, it is saved in the info code register of the latest 50 info code events. Together with
the info code event a time indicator with 7 time intervals, which indicates how long the info code has existed,
is registered.
The Wireless M-Bus signal includes the LEAK code. If the LEAK code is active, or has been active within the
latest 30 days, a time indicator with 7 time intervals will indicate how long the info code has been active.

Table of Contents

Other manuals for Kamstrup flowIQ 3100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kamstrup flowIQ 3100 and is the answer not in the manual?

Kamstrup flowIQ 3100 Specifications

General IconGeneral
BrandKamstrup
ModelflowIQ 3100
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals