flowIQ® 3100 TECHNICAL DESCRIPTION
Kastup A/S • Tehial Desiptio • 5512-1242_D1_GB • 09.2016
10.2 Monthly and daily loggers
The table below shows which registers are logged on the first day of the month, and which are logged
every day. The daily logger is an absolute log, i.e. current meter reading is logged every day.
Logging time, year, month and day
Current meter reading (legal)
Accumulated number of operating hours
Volume during reverse flow
Date stamp of max. flow during period
Value for max. flow during period
Date stamp of of min. flow during period
Value of min. flow during period
The lowest measured water
temperature during period
Volume weighted average water
temperature during period
The highest measured water
temperature during period
The lowest measured ambient/meter
temperature during period
Time weighted average ambient
temperature during period
The highest measured ambient
temperature during period
*)
Applies only for meter sizes 1.6, 2.5 and 4.0 m
3
/h
10.3 Hour counter
Each info code, DRY, REVERSE, LEAK and BURST, has a corresponding hour counter. The hour counters are
incremented by one every hour, counted on the meter's clock, the corresponding info code is active.
Counting starts immediately the first time the info code is active within the hour in question. Even though
the info code occurs more than once within an hour, the counter is only incremented once. If the info code
remains active for several hours, the counter is incremented by one for each hour. The increment is
independent of how small a part of the hour the info code is active.
Please note: The info code DRY is set in two steps, the increment of the hour counter follows the second
step. See paragraph
Info register
The hour counters cannot be accessed directly but are represented in the info register in coarse resolution.
See paragraph Info register
No hours are counted as long as the meter is in transport mode.