6.7 Min. and max. flow and power, V1
MULTICAL
602 registers both minimum and maximum flow and power both on a monthly and on a yearly basis.
These values can be read in full via data communication. In addition, a small number of monthly and yearly registers
can be read on the display depending on the selected DDD code.
Min. and Max. registration comprises following flow and power values including date.
Registration type:
Max. data Min. data Yearly data Monthly data
Max. this year (since last target date)
Max. yearly data, up to 15 years back
Min. this year (since last target date)
Min. yearly data, up to 15 years back
Max. this month (since last target date)
Max. monthly data, up to 36 months back
Min. this month (since last target date)
Min. monthly data, up to 36 months back
All max. and min. values are calculated as largest and smallest average of a number of current flow or power
measurements. The average period used for all calculations are selected in the interval 1…1440 min. in jumps in 1
min. (1440 min. = 1 full day).
The average period and target date are stated in connection with orders or re-configured by means of METERTOOL.
Where nothing has been stated when the order was placed the average period is set at 60 min. and the target date
is set at the standard applying for the country code used.
In connection with commencement of a new year or month the max. and min. values are stored in the data logger
and the current max. and min. registers are "reset" according to the selected target date and the internal clock and
calendar of the meter.
"Reset" is made by putting the max. value at zero and min. value at 10000.0 kW at e.g. CCC=119.
Date for year-to-date max.
Value for year-to-date max.
Date for min. in the current month
Value for min. in the current month

Table of Contents

Other manuals for Kamstrup MULTICAL 602

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kamstrup MULTICAL 602 and is the answer not in the manual?

Kamstrup MULTICAL 602 Specifications

General IconGeneral
Flow SensorUltrasonic
DisplayLCD
Battery LifeUp to 16 years
CommunicationM-Bus, Wireless M-Bus
ApprovalMID class 2, EN 1434
AccuracyClass 2
Pressure RatingPN16
ApplicationHeating and cooling systems
Temperature Range0°C to 180°C

Related product manuals