9.7 Exchanging the supply unit
The power supply unit for MULTICAL
®
602 can be exchanged from mains supply to battery or vice versa as the needs
at the utility change. In this way, mains supplied meters can be exchanged for battery meters with advantage in
connection with buildings in the course of construction, as the mains supply may be unstable or lack periodically.
Previous versions of MULTICAL
®
602 (before 2014-04-01) use screw terminals for connection of the supply unit.
When replacing the supply unit in previous versions, cut off the plug and strip the cable insulation before
connecting the cables to the screw terminals.
Exchange from battery to mains supply does not require reprogramming, as MULTICAL
®
602 does not contain an
information code for worn out batteries.
However, exchange from mains supply to battery must not be made on MULTICAL
®
602 with the following base
modules:
MULTICAL 602
Type 602-
Base module
Radio Router/
p
ulse in
p
uts
21
Prog. data logger + RTC + 4…20 mA in
p
uts +
p
ulse in
p
uts
22
0/4…20 mA out
p
uts
23
LonWorks +
p
ulse in
p
uts
24
ZigBee 2.4 GHz int.ant. +
p
ulse in
p
uts
60
Metasys N2 (RS485 +
p
ulse in
p
ts
62
SIOX module (Auto detect Baud rate)
64
BACnet MS/TP +
p
ulse in
p
uts
66
Modbus RTU +
p
ulse in
p
uts
67
GSM/GPRS module (GSM6H)
80
3G GSM/GPRS modul (GSM8H)
81
High Power Radio Router +
p
ulse in
p
uts
84
See paragraph 10.1.5 re supply options for top and base modules.
9.8 Mains supply cables
MULTICAL
602 is available with mains cables H05 VV-F for either 24 V or 230 V (l=1.5 m):
Mains cable, type 5000-286 (2x0.75 mm²), max. 6 A fuse
”H05 VV-F” is the designation for a heavy PVC cable, that stands max. 70C. The supply cable must therefore be
installed with a sufficient distance to hot pipes and the like.