2 Technical Data
2.1 Approved meter data
Standard EN 1434:2007, prEN 1434:2009 and OIML R75:2002
EU directives Measuring Instrument Directive, Low Voltage Directive,
Electromagnetic Compatibity Directive
Heat meter approval D
The stated minimum temperatures
apply to the type approval only.
The meter has no cut-off for low
temperature and thus measures as low
temperatures as
0.01C and 0.01 K.
Temperature range : 2C…180C
Differential range : 3 K…170 K
Cooling meter
Temperature range : 2C…50C
Differential range : 3 K…40 K
Accuracy E
C
(0.5 +
min
/) %
Temperature sensors -Type 602-A Pt100 – EN 60 751, 2-wire connection
-Type 602-B and 602-D Pt500 – EN 60 751, 4-wire connection
-Type 602-C Pt500 – EN 60 751, 2-wire connection
Compatible flow sensor types -ULTRAFLOW
-Electronic meters with an active 24 V pulse output
-Mechanical meters with an electronic pick-up unit
-Mechanical meters with a Reed switch
Flow sensor sizes kWh qp 0.6 m
3
/h…15 m
3
/h
MWh qp 0.6 m
3
/h…1500 m
3
/h
GJ qp 0.6 m
3
/h…3000 m
3
/h
EN 1434 designation Environmental class A and C
MID designation Mechanical environment: Class M1
Electromagnetic environment: Class E1 and E2
5…55 °C, non condensing, closed location (indoor installation)