6.13 Data loggers
MULTICAL
602 contains a permanent memory (EEPROM), where the results of a number of various data loggers
are stored. The meter contains the following data loggers:
Data logging interval Data logging depth Logged value Logger read-out
Yearly logger 15 years Counter registers LogView/MT Pro
Monthly logger 36 months Counter registers LogView/MT Pro
Daily logger 460 days Consumption (increase)/day
LogView/MT Pro
Hourly logger 1392 hours Consumption (increase)/hour
LogView/MT Pro
Programmable data logger
top module 67-0B and base
module 67-00-22
1080 loggings
Logging interval 1-1440 min.
(e.g. 45 days' hour loggings or
11 days' 15 min. loggings)
30 registers and values
AMR *),
LogView/MT Pro
Info logger
50 events (36 events can be
displayed)
Info code, date, time and
energy (E1/E3) **)
LogView/MT Pro
*) Example of AMR (Automatic Meter Reading) for the data logger is GSM/GPRS. See chapter 13.4 about LogView.
**)
Only info code and date appear from the display.
The loggers are static and therefore the register types cannot be changed, furthermore, the logging intervals are
fixed. When the last record has been written in the EEPROM the oldest one is overwritten.
6.13.1 Yearly, monthly, daily and hourly loggers
Following registers are logged every year and every month on target date as counter values. In addition, the
increases of the day and the hour are logged at midnight.
Register type Description
Yearly
logger
Monthly
logger
Daily
logger
Hourly
logger
67-0B
67-00-22
Prog.
logger
Date (YY.MM.DD) Year, month and day for logging times
Clock (hh.mm.ss.) Time
- -
- -
Log Info Status, quality stamping of log record
- -
- -
E1 E1=V1(T1-T2)k Heat energy
E2 E2=V2(T1-T2)k Heat energy
E3 E3=V1(T2-T1)k Cooling energy
E4 E4=V1(T1-T3)k Inlet energy
E5 E5=V2(T2-T3)k Returned energy or tap from outlet
E6 E6=V2(T3-T4)k Tap water energy, separate
E7 E7=V2(T1-T3)k Tap water energy from inlet
E8 E8=m
3
x T1 (inlet)
-
E9 E9=m
3
x T2 (outlet)
-
TA2 Tariff register 2
-
-
-
TA3 Tariff register 3
-
-
-
V1 Volume register for Volume 1
V2 Volume register for Volume 2
VA Extra water or electricity meter connected to Input A
VB Extra water or electricity meter connected to Input B
M1 Mass corrected V1
- -
M2 Mass corrected V2
- -
INFO Information code
DATE FOR MAX. FLOW V1 Date stamp for max. flow in the period
-
-
-
MAX. FLOW V1 Value for max. flow in the period
-
-
-
DATE FOR MIN. FLOW V1 Date stamp for min. flow in the period
-
-
-
MIN. FLOW V1 Value for min. flow in the period
-
-
-
DATE FOR MAX. POWER V1 Date stamp for max. power in the period
-
-
-