6 Kamstrup A/S • 5512603_C1_GB_03.2016
MULTICAL® 801
1 General information
Please read this guide before installing the energy meter.
If the meter is installed incorrectly, Kamstrup’s warranty obligations
will no longer apply.
Plese note tht the following instlltion conditions must be obeyed:
- Pressure stge ULTRAFLOW®: PN16/PN25/PN40, see mrking. Mrking
of flow prt does not cover included
ccessories.
- Pressure stge Kmstrup
sensor set type DS: PN16
- Pressure stge Kmstrup
pocket sensors type PL: PN25/PN40 - depending on type
If the medium temperture exceeds 90 °C we recommend using flnge
meters.
Plese mke sure tht MULTICAL® 801 is connected to correct voltge, either
230 VAC or 24 VAC. See the mrking t terminls 27 nd 28 t the bottom
left.
MULTICAL® 801 must be seled with sel nd wire or seling lbel fter
mounting.