Functional Description
Chapter Section Page
Date
Operating and Appliance Displays
Adr.
min max
default
Adr.
min max
default
Adr.
min max
default
Adr.
min max
default
200Bh
ru.11 DC-link voltage
1
V
-
999200
Display of actual DC-link voltage. Typical values are for
normal operation: 230V-class approx. 300-330V in case of fault (E.OP): 230V-class approx.390V
400V-class approx. 530-620V 400V-class approx.800V
200Ch
ru.12 DC-link voltage peak value
1
%
-
999200
ru.12 allows the detection of short-time voltage rises within an operating cycle. For that the highest detected value of
ru.11 is stored in ru.12. The peak value memory is cleared by pressing the keys UP or DOWN or by bus by writing any
chosen value to the address of ru.12. The disconnection of the inverter also results in a clearing of the memory.
200Dh
ru.13 Output voltage
1
V
-
9990
Display of actual output voltage
200Eh
ru.14 Input terminal status
1
-
-
2550
Display of the actual triggered digital inputs. Whether the input is inverted or the internal acceptance takes place
through edge triggering or strobe is irrelevant for the display. According to following table a certain decimal value is
given out for each digital input. If several inputs are triggered then the sum of their decimal values is displayed.
Bit -No. Decimal value Input Terminal
0 1 ST (control release) 19
1 2 RST (Reset) 20
2 4 F (rotation forward) 10
3 8 R (rotation reverse) 11
4 16 I1 (prog. input 1) 4
5 32 I2 (prog. input 2) 5
6 64 I3 (prog. input 3) 6
7 128 I4 (prog. input 4) 7