6
115
24.06.02
KEB COMBIVERT F5-G / B
Name: Basis
6
Functional Description
© KEB Antriebstechnik, 2002
All rights reserved
Chapter Section PageDate
Operating and Appliance Data
Adr.
min max
default
022Ah
ru.42 Modulation factor
1
%
-
1100
The modulation factor shows the output voltage in percent. 100 % correspond to the input voltage (no-load). At a value
of > 100 % the inverter works with overmodulation.
Adr.
min max
default
Adr.
min max
default
Adr.
min max
default
Adr.
min max
default
0227h
ru.39 OL - counter display
1
%
-
1000
In order to preclude „E.OL“ - errors by too high load (load reduction in due time), the internal count of the OL-counter can
be made visible with this indication. At 100 % the inverter switches off with error „E.OL“. The error can be reset only after
a cooling time (blinking display „E.nOL“).
0226h
ru.38 Power module temperature
1
°C
-
1500
ru.38 shows the current power moduls temperature of the inverter.
0228h
ru.40 Operating hours meter
1
h
-
655350
The operating hours meter shows the time the inverter was switched on. The indicated value comprises all operating
phases. On reaching the maximum value (approx. 7.5 years) the indication remains on the maximum value.
0229h
ru.41 Modulation hours meter
1
h
-
655350
The modulation hours meter shows the time the inverter was active (power modules controlled). On reaching the maximum
value (approx. 7.5 years) the indication remains on the maximum value.
Adr.
min max
default
022Bh
ru.43 Timer 1 / display
0.01
s / h
-
655.350
The count of the free-programmable timer 1 is indicated. The display is done either in seconds, in hours or in slopes/100
(see LE.21). The counter can a adjusted to any chosen value by keyboard or bus. The programming of the counter is