6 4
KEB COMBIVERT F5-G / B
10
Name: Basis
06.02.02
© KEB Antriebstechnik, 2002
All rights reserved
Functional Description Set Value and Ramp Adjustment
Chapter Section Page Date
Fixed-value rotation direction
source (oP.18)
With oP.18 it is defined how the direction of rotation is determined in case of active
fixed frequency. The function and the value range correspond to oP.1.
oP.18 Rotation direction source for fixed frequencies
0 digital via oP.2; setpoint 0-limited
1 digital via oP.2; setpoint absolute
2 terminal strip F/R; setpoint 0-limited
3 terminal strip F/R; setpoint absolute
4 terminal strip Run/Stop; setpoint 0-limited
5 terminal strip Run/Stop; setpoint absolute
6 setpoint-dependent with LS-recognition
7 setpoint-dependent without LS-recognition
8 control word SY.50; 0-limited
9 control word SY.50; 0-absolute
Fixed-value input selection 1 and 2
(oP.19; oP.20)
Fixed frequency 1...3
(oP.21, oP.22, oP.23)
The three fixed frequencies oP.21...23 are set-programmable and can be adjusted
in the range of -400...400 Hz.
Bit -No. Decimal value Input Terminal
0 1 ST (Prog. input „Control release/Reset“) X2A.16
1 2 RST (Prog. input „Reset“) X2A.17
2 4 F (Prog. input „Forward“) X2A.14
3 8 R (Prog. input „Reverse“) X2A.15
4 16 I1 (Prog. input 1) X2A.10
5 32 I2 (Prog. input 2) X2A.11
6 64 I3 (Prog. input 3) X2A.12
7 128 I4 (Prog. input 4) X2A.13
8 256 IA (Internal input A) none
9 512 IB (Internal input B) none
10 1024 IC (Internal input C) none
11 2048 ID (Internal input D) none