Product DescriptionSummary
Chapter Section Page Date
2.1.6 Unit Sizes 230V-Class
The following technical specifications refer to 2-/4-pole standard motors. In case of
different pole numbers the frequency inverter must be dimensioned for the rated
motor current. With regard to special or medium frequency motors, please contact
KEB.
The power losses always refer to the max. switching frequency. If the switching
frequency is reduced, the power loss is reduced as well.
Site altitude max. 2000 m. For altitudes of 1000 m or more above N.N. a power reduction
of 1 % per 100m must be taken into account.
2.1.5 Validity of
Specifications
1) With the regulated systems F5-M as well as F5-S 5% are to be subtracted as control reserve
2) This data is only valid for units with integrated PFC (see "unit identification")
3) Max. current before the responding of the OL2-function (only F5-M; F5-S; F5-A)
4) Recommended minimum cross section for rated power and a cable length of upto 100m (copper)
5) This data is only valid for units with internal brake transistor GTR 7 (see "unit identification")
6) At units with integrated filter (see "unit identification"):
up to max. 5m line length and 4kHz operating frequency = Limit Value B (EN 55011)
up to max. 10m line length and 16kHz operating frequency = Limit Value A (EN 55022)
Inverter Size 05 07 09 10 12 13 14
Housing size A ABBDBDDEE
Phases 11311313131313 3 3 3
Output rated power [kVA] 0,9 1,6 2,8 4,0 6,6 9,5 13
Max. rated motor power [kW] 0,37 0,75 1,5 2,2 4,0 5,5 7,5
Output rated current [A] 2,3 4 7 10 16,5 24 33
Max. short time current
1)
[A] 4,1 7,2 12,6 18 29,7 36 49,5
OC-tripping current [A] 5,0 8,6 15,1 21,6 35,6 43 59
Input rated current [A] 4,6 4,6 3,2 8,0 8,0 5,6 14 9,8 14 9,8 20 14 20 14 23 31 43
Input rated current
2)
[A] 3,7 6,4
Real input rated power
2)
[kW] 0,85 1,5
Max. permissible mains fuse (inert) [A] 10 16 10 20 16 20 16 20 16 25 20 25 20 25 35 50
Rated operating frequency [kHz] 4 16 8 16 16 8 16 8 8 4
Max. operating frequency [kHz] 8 16 8 16 16 16 16 16 16
Power loss at rated operation [W] 30 50 55 65 90 130 105 170 210 290 350
Power loss at rated operation
2)
[W] 85 130
Stall current at 4kHz
3)
[A] 2,3 4 7 10 16,5 24 33
Stall current at 8kHz
3)
[A] 2,3 4 7 10 16,5 24 24
Stall current at 16kHz
3)
[A] 2,3 4 7 8,5 10 10 16,8 16,8
Max. heat sink temperature TOH [°C] 90
Motor line cross section
4)
[mm²] 1,5 1,5 1,5 2,5 1,5 2,5 1,5 2,5 1,5 4 2,5 4 2,5 4 6 10
Min. braking resistor
5)
[Ohm] 100 56 100 56 47 33 27 16 16
T
y
p. brakin
g
resistor
5)
[Ohm] 180 100 100 68 56 47 22 22
Max. braking current [A] 4,5 7,5 4,5 7,5 9,5 12 15 25 25
Overload curve 1
Tightening torque for terminal strip [Nm] 0,5 1,2
Mains voltage [V] 180...260 ±0 (230 V rated voltage)
Mains frequency [Hz] 50 / 60 +/- 2
Output voltage
[V]
3 x 0...U Mains (3 x 0...255V
2)
)
Output frequency [Hz] see control board
Max. shielded motor line length at 4 kHz
6)
[m]103010100 100 100
Max. shielded motor line len
g
th at 8 kHz
6)
[m]10201050 100 100
Max. shielded motor line len
g
th at 16kHz
6)
[m] 10 20 40 100
Storage temperature [°C] -25...70 °C
Operating temperature [°C] -10...45 °C
Design / type of protection IP20
Relative humidity max. 95% without condensation
EMC tested according to product standard EN 61800-3