KEB COMBIVERT F5
Name: Basis
10.04.02
2
© KEB Antriebstechnik, 2002
All Rights reserved
Product Description Summary
Section PageDate Chapter
2.1.7 Unit Sizes 400V-Class
1) With the regulated systems F5-M as well as F5-S 5% are to be subtracted as control reserve.
2) Max. current before the responding of the OL2-function (only F5-M; F5-S; F5-A)
3) Recommended minimum cross section for rated power and a cable length of upto 100m (copper)
4) This data is only valid for units with internal brake transistor GTR 7 (see "unit identification")
5) At mains voltage ≥ 460V multiply the nominal current with factor 0,86.
Inverter Size 05 07 09 10 12 13 14
Housing size B B B D B D B D E D E E G
Phases 3 3 3 3 3 3 3
Output nominal power [kVA] 0,9 1,8 2,8 4,0 6,6 8,3 11
Max. rated motor power [kW] 0,37 0,75 1,5 2,2 4,0 5,5 7,5
Output nominal current [A] 1,3 2,6 4,1 5,8 9,5 12 16,5
Max. short time current
1)
[A] 2,3 4,7 7,4 10,4 17 21,6 29,7 24,8
OC-tripping current [A] 2,8 5,6 8,9 12,5 21 25,9 35,6 29,7
Nominal input current [A] 1,8 3,6 6 8 13 17 23
Max. permissible mains fuse (inert) [A] 16 16 16 16 20 25 25
Rated operating frequency [kHz] 16 16 8 8 16 4 8 16 4 16 8 16
Max. operating frequency [kHz] 16 16 16 16 4 16 16 16
Power loss at nominal operating [W] 60 90 80 105 120 170 150 185 300 185 250 320 260
Stall current at 4kHz
2)
[A] 1,3 2,6 4,1 5,8 7,6 9,5 12 16,5
Stall current at 8kHz
2)
[A] 1,3 2,6 4,1 5,8 – 9,5 9,5 12 16,5
Stall current at 16kHz
2)
[A] 1,3 2,6 3,5 4,9 5,8 – 5,8 9,5 5,8 12 10 12
Max. heat sink temperature TOH [°C] 90
Motor line cross section
3)
[mm²] 1,5 1,5 1,5 1,5 2,5 4 4
Min. braking resistor
4)
[Ohm] 390 120 120 82 82 56 39 39
Typ. braking resistor
4)
[Ohm] 390 390 270 270 150 100 82
Max. braking current [A] 2,2 7,5 7,5 10 10 15 21 21
Overload curve 1
Tightening torque for terminals [Nm] 0,5 1,2
Mains voltage
5)
[V] 305...500 ±0 (400 V Nominal voltage)
Mains frequency [Hz] 50 / 60 +/- 2
Output voltage [V] 3 x 0...U Mains
Output frequency [Hz] see Control board
Max.shielded motor line length at 4 kHz [m] 10 10 100 100 50 100
Max.shielded motor line length at 8 kHz [m] 8 8 30 50 100 – 100
Max.shielded motor line length at 16 kHz [m] 4 5 10 10 20 – 100
Storage temperature [°C] -25...70 °C
Operating temperature [°C] -10...45 °C
Model / protective system IP20
Relative humidity max. 95% without condensation
EMC tested according to product standard EN 61800-3
Climatic category 3K3 in accordance with EN 50178
0,5