Product DescriptionSummary
Chapter Section Page Date
1) With the regulated systems F5-M as well as F5-S 5% are to be subtracted as control reserve.
2) Max. current before the responding of the OL2-function (only F5-M; F5-S; F5-A)
3) Recommended minimum cross section for rated power and a cable length of upto 100m (copper)
4) This data is only valid for units with internal brake transistor GTR 7 (see "unit identification")
5) At mains voltage ≥ 460V multiply the nominal current with factor 0,86.
Inverter Size 15 16 17 18 19
Housing size EGHGHGHHRHR
Phases 3 3333
Output nominal power [kVA] 17 23 29 35 42
Max. rated motor power [kW] 11 15 18,5 22 30
Output nominal current [A] 24 33 42 50 60
Max. short time current
1)
[A]36 49,5637590
OC-tripping current [A] 43 59 75 90 108
Nominal input current [A] 31 43 55 65 66
Max. permissible mains fuse (inert) [A] 35 50 63 80 80
Rated operating frequency [kHz] 4 8 16 8 16 4 8 8 16 4 8
Max. operating frequency [kHz] 16 16 16 16 16
Power loss at nominal operating [W] 350 290 360 310 490 360 470 610 850 540 750
Stall current at 4kHz
2)
[A]24 33425060
Stall current at 8kHz
2)
[A]16192421,53321,43045503960
Stall current at 16kHz
2)
[A] 10 8,5 15 9,5 20 – 13,5 20 40 18 27
Max. heat sink temperature TOH [°C]
Motor line cross section
3)
[mm²] 6 10 16 25 25
Min. braking resistor
4)
[Ohm]3939222522252213 9 13 9
Typ. braking resistor
4)
[Ohm]56 39282216
Max. braking current [A]2121373037303763886388
Overload curve 1
Tightening torque for terminals [Nm] 2,5 1,2 2,5 1,2 2,5 6 2,5 6
Mains voltage
5)
[V] 305...500 ±0 (400 V Nominal voltage)
Mains frequency [Hz] 50 / 60 +/- 2
Output voltage [V] 3 x 0...U Mains
Output frequency [Hz] see Control board
Max. shielded motor line length [m] 100
Storage temperature [°C] -25...70 °C
Operating temperature [°C] -10...45 °C
Model / protective system IP20
Relative humidity max. 95% without condensation
EMC tested according to product standard EN 61800-3
Climatic category 3K3 in accordance with EN 50178
90
1,2