KEB COMBIVERT F5
10
Name: Basis
10.04.02
© KEB Antriebstechnik, 2002
All Rights reserved
Product DescriptionSummary
Chapter Section Page Date
Inverter Size 25 26 27
Housing size U U U
Phases 333
Output nominal power [kVA] 145 173 208
Max. rated motor power [kW] 110 132 160
Output nominal current [A] 210 250 300
Max. short time current
1)
[A] 263 313 375
OC-tripping current [A] 315 375 450
Nominal input current [A] 231 275 330
Max. permissible mains fuse (inert) [A] 315 400 450
Rated operating frequency [kHz] 4 4 2
Max. operating frequency [kHz] 8 8 8
Power loss at nominal operating [W] 2300 2800 3100
Stall current at 4kHz
2)
[A] 210 250 240
Max. heat sink temperature TOH [°C] 90
Motor line cross section
3)
[mm²] 95 120 150
Min. braking resistor
4)
[Ohm] 4
Typ. braking resistor
4)
[Ohm] 4
Max. braking current [A] 200
Overload curve 2
Tightening torque for terminals [Nm] 25
Mains voltage
5)
[V] 305...500 ±0 (400 V Nominal voltage)
Mains frequency [Hz] 50 / 60 +/- 2
Output voltage [V] 3 x 0...U Mains
Output frequency [Hz] see Control board
Max. shielded motor line length [m] 50
Storage temperature [°C] -25...70 °C
Operating temperature [°C] -10...45 °C
Model / protective system IP20
Relative humidity max. 95% without condensation
EMC tested according to product standard EN 61800-3
Climatic category 3K3 in accordance with EN 50178
1) With the regulated systems F5-M as well as F5-S 5% are to be subtracted as control reserve.
2) Max. current before the responding of the OL2-function (only F5-M; F5-S; F5-A)
3) Recommended minimum cross section for rated power and a cable length of upto 100m (copper)
4) This data is only valid for units with internal brake transistor GTR 7 (see "unit identification")
5) At mains voltage ≥ 460V multiply the nominal current with factor 0,86.