EasyManuals Logo

KEB COMBIVERT G6 Instructions For Use And Installation

KEB COMBIVERT G6
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #24 background imageLoading...
Page #24 background image
3 Technical Data
3.1 Operating conditions
3.1.1 Climatic conditions
Storage Standard Class Notes
Surrounding temperature EN 60721-3-1 1K4 -25…55 °C
Relative humidity EN 60721-3-1 1K3 5…95 % (without condensation)
Storage height max. 3000 m above sea level
Transport Standard Class Notes
Surrounding temperature EN 60721-3-2 2K3 -25…70 °C
Relative humidity EN 60721-3-2 2K3 95 % at 40 °C (without condensation)
Operation Standard Class Notes
Surrounding temperature EN 60721-3-3 3K3
5…40 °C (extended to -10…45 °C)
A derating of 5% per 1 K must be considered
from 45 °C to max. 55 °C.
Coolant inlet
temperature
Air 5…40 °C (-10…45 °C)
Water 5…40 °C
Relative humidity EN 60721-3-3 3K3 5…85 % (without condensation)
Version and degree of
protection
EN 60529 IP20
Protection against foreign material > ø12.5 mm
No protection against water
Non-conductive pollution, occasional conden-
sation when PDS is out of service.
Site altitude
max. 2000 m above sea level
With site altitudes over 1000 m a derating
of 1 % per 100 m must be taken into con-
sideration.
With site altitudes over 2000 m, the control
board to the mains has only basic isola-
tion. Additional measures must be taken
when wiring the control.
Table 2: Climatic ambient conditions
24

Table of Contents

Other manuals for KEB COMBIVERT G6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT G6 and is the answer not in the manual?

KEB COMBIVERT G6 Specifications

General IconGeneral
BrandKEB
ModelCOMBIVERT G6
CategoryDC Drives
LanguageEnglish

Related product manuals