3 Technical Data
3.1 Operating conditions
3.1.1 Climatic conditions
Storage Standard Class Notes
Surrounding temperature EN 60721-3-1 1K4 -25…55 °C
Relative humidity EN 60721-3-1 1K3 5…95 % (without condensation)
Storage height max. 3000 m above sea level
Transport Standard Class Notes
Surrounding temperature EN 60721-3-2 2K3 -25…70 °C
Relative humidity EN 60721-3-2 2K3 95 % at 40 °C (without condensation)
Operation Standard Class Notes
Surrounding temperature EN 60721-3-3 3K3
5…40 °C (extended to -10…45 °C)
A derating of 5% per 1 K must be considered
from 45 °C to max. 55 °C.
Coolant inlet
temperature
Air 5…40 °C (-10…45 °C)
Water 5…40 °C
Relative humidity EN 60721-3-3 3K3 5…85 % (without condensation)
Version and degree of
protection
EN 60529 IP20
Protection against foreign material > ø12.5 mm
No protection against water
Non-conductive pollution, occasional conden-
sation when PDS is out of service.
Site altitude
max. 2000 m above sea level
With site altitudes over 1000 m a derating
of 1 % per 100 m must be taken into con-
sideration.
With site altitudes over 2000 m, the control
board to the mains has only basic isola-
tion. Additional measures must be taken
when wiring the control.
Table 2: Climatic ambient conditions