5 Maintenance
5.1 General
Allworkmayonlybedonebyqualiedpersonnel.The security must be ensured as
follows:
Disconnect power supply at MCCB
Secure against restarting
Await discharge time of capacitors
(if necessary controlling by measurement at „+“ and „-“, respectively at „++“ and „--“)
Ensure voltage free status by measurement
In order to avoid premature ageing and avoidable malfunctions, the measures men-
tioned below must be carried out in the appropriate cycle.
Cycle Function
Constant
Pay attention to unusual noises of the motor (e.g. vibrations) as well as
of the drive converter (e.g. fan).
Pay attention to unusual smells of the motor or drive converter (e.g.
evaporation of capacitor electrolyte, braise of the motor winding).
Monthly
Check unit for loose screws and plugs and if necessary tighten up.
Clean drive converter from dirt and dust deposits. Pay attention espe-
ciallytocoolingnsandprotectivegridofthefans.
Examineandcleanextractedairlterandcoolingairlterofthecon-
trol cabinet.
Examine function of the fans of the KEB COMBIVERT. The fan must
be replaced in case of audible vibrations or squeak.
Make a visual leak test of the cooling circuit for water-cooled drive
converters.
Table 10: Maintenance cycles