82                             Keysight N9927-90001 User’s Guide
TDR (Time Domain Reflectometry) - Option 215
TDR Measurement Settings
Start Frequency – Start frequency that is used to calculate TDR. 
Stop Frequency – Stop frequency that is used to calculate TDR.
Range Resolution. Indicates the accuracy of the distance to fault 
measurement. For example, with range resolution of 500 mm, if the distance to 
fault is 10 meters, this value could be inaccurate by +/- 500 mm or between 
9.5 to 10.5 meters. This value is calculated from frequency span / resolution 
(points).
Response Resolution, not displayed, indicates the distance that could be 
between two faults and still show as separate faults. Learn more in Window 
Settings in “Window Settings” on page 80.
Maximum Distance. The distance that could be viewed with the current 
settings. Defined by: Vf*c*Points/(2*Bandwidth) where:
— Vf = velocity factor
— c = speed of light
— Points = resolution
— Bandwidth = frequency range
Alias-free Range (On/Off)
—On = No Alias images
— Off = Alias images may appear in the response.
About Alias Faults
An alias fault is not a true device response. An alias fault appears because of 
the method used to convert frequency to time.
On the TDR Settings page (above) the c - Alias-free Range = Off setting 
indicates alias images MAY appear on the screen.
Shorter stop distances (less than 10 meters) and a higher resolution (1001 
points) will be more likely to result in Alias-free Range = Off.
When the Alias-free Range = Off, the following procedure will help to 
determine if a response is true or an alias response: 
1. Put a marker on the response in question and note the distance to the 
fault. 
2. Change the start or stop distance. 
A true fault response will not move in distance. That is, if a true fault is present 
at 10.3 meters, changing the stop distance from 15 m to 20 m will not move 
the fault; the fault will remain at 10.3 meters. However, an alias response will 
appear to move.