Appendix C: Applications 
224  P/N 3102351-EN • REV 005 • ISS 28DEC18 
Message Line 1: SMOKE_<N>, where <N> can be the device address or other number 
Base Type: Sounder 
Follow: Head 
3.  Configure the RM1 or CT1 module as follows: 
Device type: Monitor 
Message Line 1: 24VDC_RISER 
Programming sounder bases for a T3T4 Fire Alarm/CO emergency 
signaling application per NFPA 720, UL 2017  
Figure 58: Wiring the sounder base for a T3T4 Fire/CO alarm 
 
  AUX riser – 
  Use  a  power-
VDC power supply that is UL/ULC Listed 
for fire protective signaling system. 
(4)  RM1 module or equivalent  
(5)  SLC OUT + 
(6)  SLC OUT − 
(7)  SLC IN +