Appendix C: Applications 
P/N 3102351-EN • REV 005 • ISS 28DEC18  225 
Notes 
•  For PS/PD, PHS/PHD, IPHS, and SD detectors configured as “Supervisory Non-latching” 
device type or for PCOS/PCD detectors (smoke element) configured as “Smoke 
Supervisory Non-latching” device type, if the base is Relay/Sounder, then the follow type 
option cannot be configured as “Head.” The follow type in this case should be set to 
“Alarm.” 
•  The following procedure must be done using the Configuration Utility (CU). 
To program the sounder base for T3T4 Fire/CO: 
1.  Set the panel’s Event Notification option to Device/Zone. 
2.  Configure the detectors as follows: 
Message Line 1: DETECTOR_<N>, where <N> can be the device address or other number 
Device Type: Primary sensor type + CO alarm 
Base Type: SBT/ABDT Sounder 
Follow: None, Head, Alarm, Alm + Vrfy, or Alm + PreAlm 
  Follow CO: No or Yes (only displays if Follow is set to Alarm, Alm + Vrfy, or Alm + PreAlm) 
3.  Configure the RM1 or CT1 module as follows: 
Device type: Monitor 
Message Line 1: 24VDC_RISER 
Message Line 2: SOUNDER_RLY_1 
4.  Configure Correlation Group 001 as follows: 
Add/Remove Zone: As required 
Add/Remove NAC: As required 
Add/Remove Device: Add all alarm signal initiating devices corresponding T3T4 device 
Channels as described below 
To create correlations for T3T4: 
1.  Channel 1 must be correlated with proper SBT/ABDT sounder base as output to any 
primary alarming type inputs. 
2.  Channel 2 can be correlated with proper SBT/ABDT sounder base as output to secondary 
element (CO) of GSA detectors. 
3.  If both Channel 1 and Channel 2 are correlated as outputs to a sounder base, then 
Channel 1 pattern overwrites the Channel 2 pattern.