Chapter 2: Front panel programming 
P/N 3102351-EN • REV 005 • ISS 28DEC18  71 
Table 21: Auto programming — Dialer options [1] 
Option  Description 
Account 1  Account ID: Enter the four-digit ID code for account 1 Note, if you do not change the 
default of FFFF, no events will be sent.) 
Primary receiver number: Enter the primary receiver’s phone number. Up to 20 digits (0-9, 
*, #, and ,). The comma causes a two-second delay in dialing. The number or hash symbol 
(#) and the asterisk symbol (*) are used with calling feature codes and services. Consult 
your telephone service provider. 
Secondary receiver number: Enter the secondary receiver’s phone number. Up to 20 digits 
(0-9, *, #, and ,). The comma causes a two-second delay in dialing. 
Format: CID 
CID: Contact ID is the alarm format that the monitoring facility (DACR) will receive. See 
“Default contact ID event codes” on page 46. 
Event notification: Set event notification (event reporting) to: 
Device: Only device information is reported or transmitted, no zone information. This 
setting uses default device event notification settings for reporting events. See “Factory 
default settings” on page 42. 
Zone: When a device is a member of a zone, only the zone information is reported or 
transmitted, no device information. This setting uses default zone event notification 
settings for reporting events. See “Factory default settings” on page 42. 
Event: Only the event type (alarm, supervisory, trouble, etc.) is reported or transmitted, no 
device or zone information. This setting uses the default CMS event notification settings 
for reporting events. See “Factory default settings” on page 42. 
Account 2  Account ID: Enter four-digit ID code for account 2. 
Primary receiver number: Enter the primary receiver’s phone number (up to 20 digits). 
Secondary receiver number: Enter the secondary receiver’s phone number (up to 20 
digits). 
Format: CID 
CID: Contact ID is the alarm format that the monitoring facility (DACR) will receive. See 
“Default contact ID event codes” on page 46. 
Event notification: Set event notification (event reporting) to: 
Device: Only device information is reported or transmitted, no zone information. This 
setting uses default device event notification settings for reporting events. See “Factory 
default settings” on page 42. 
Zone: When a device is a member of a zone, only the zone information is reported or 
transmitted, no device information. This setting uses default zone event notification 
settings for reporting events. See “Factory default settings” on page 42. 
Event: Only the event type (alarm, supervisory, trouble, etc.) is reported or transmitted, no 
device or zone information. This setting uses the default CMS event notification settings 
for reporting events. See “Factory default settings” on page 42. 
[1]  Dialer options are displayed only if a dialer is installed on the panel.