Chapter 2: Front panel programming 
72  P/N 3102351-EN • REV 005 • ISS 28DEC18 
NET options 
Table 22 describes the network options used to set up the Ethernet card. 
Table 22: Auto programming — NET options 
Option  Description 
Account ID 
Enter the six-digit code for the central monitoring station (CMS) account. 
IP  Enter the IP address for the CMS. 
Event notification  Set event notification (event reporting) to: 
Device: Only device information is reported or transmitted, no zone information. This 
setting uses default device event notification settings for reporting events. See “Factory 
default settings” on page 42. 
Zone: When a device is a member of a zone, only the zone information is reported or 
transmitted, no device information. This setting uses default zone event notification 
settings for reporting events. See “Factory default settings” on page 42. 
Event: Only the event type (alarm, supervisory, trouble, etc.) is reported or transmitted, no 
device or zone information. This setting uses the default CMS event notification settings 
for reporting events. See “Factory default settings” on page 42. 
Receiver number  Enter the CMS receiver number. Specifies the CMS receiver number to be displayed in 
the message sent to the receiver. This number is user-defined. 
Line number  Enter the CMS receiver line number. Specifies the receiver’s line number to be displayed 
in the message sent to the receiver. This number is user-defined. 
Auto programming procedure 
Use the following procedure to auto program the panel, referring to the options listed in 
Table 20 on page 69. Not all options shown are displayed on all systems. 
To auto program a panel: 
1.  Press the menu button and choose Program. 
2.  Choose Auto Program. 
3.  Enter a level two password. 
4.  When the “Current config. will be lost!,” message displays on the LCD: 
Select Continue to continue with auto programming 
— or — 
Select Cancel to return to the programming menu. 
5.  Set auto programming options. 
Note: Use the right or left arrow button rather than the Enter button to select values for 
each option. The Enter button begins the auto programming operation no matter which