Chapter 2: Front panel programming 
P/N 3102351-EN • REV 005 • ISS 28DEC18  83 
  Description 
  Select: 
001 to 025 to combine loop 1 and 2 devices in the same fast groups 
— or — 
 
101 to 125 to use separate fast groups for loop 2 devices. 
  Select Yes to enable loop 3. Select No to disable loop 3. [1] 
  Select: 
001 to 025 to combine loops 1 and 3 devices in the same fast groups 
— or — 
 
126 to 150 to use separate fast groups for loop 3 devices. 
  Select Yes to enable loop 4. Select No to disable loop 4. [1] 
  Select: 
001 to 025 to combine loops 1 and 4 devices in the same fast groups 
— or — 
 
151 to 175 to use separate fast groups for loop 4 devices. 
[1]  Displayed in multiple loop systems only. 
[2]  See “Programming fast groups for sounder bases” on page 89. 
Most options have a factory default setting that you can accept or change. 
See “Factory default settings” on page 42. 
To change loop configuration options: 
1.  Press the menu button and choose Program. 
2.  Choose Advanced Program. 
3.  Enter a level two password. 
4.  Choose Loop Configuration. 
5.  Program the options. 
Correlation group programming 
This section includes instructions for: 
•  Using fast groups 
•  Adding members to correlation groups 
•  Setting the activation count 
•  Copying members of a correlation group 
•  Removing all members from a correlation group